Transboundary notification: Northland Power

(1) Name and address of proponent:
Northland Power Inc., 30 St. Clair Ave. W., 17th Floor, Toronto, ON, M4V 3A2

(2) Latitude and longitude of proposed facility:
43o 6`25' 59" N,   79o 11`5' 85" W

(3) Distance to the Canada/U.S. border:
11 km

(4) Brief description of the proposed project (major products, process, capacity, etc):
Northland Power Inc. (NPI) will design, develop, and operate the proposed Thorold Cogeneration Project (TCP). The proposed TCP is a 255 Megawatt (MW) natural gas fired, combined cycle facility, comprised of a 160 MW natural gas fired gas turbine and a 95 MW steam turbine. The proposed TCP will be located on the premises of existing Abitibi Consolidated Canada Corp. (ACCC) paper mill in Thorold, Ontario. The facility of one NG-fired gas turbine generator (GTG), nominally rated at 160 MW, one heat recovery steam generator (HRSG) with duct firing capability (up to 100 MMBtu/hr), one steam turbine generator (STG) with nominal rating of 95 MW, two NG-fired auxiliary boilers, each with a nominal rating of 337.4 MMBtu/hr and one emergency NG-fired reciprocating engine generator set with nominal power rating of 1060 kW. One of the two auxiliary boilers will also be designed to operate on landfill gas (LFG). The LFG, which is to be taken from the existing Walker Landfill, would account for 150 MMBtu/hr, High Heating Value (HHV) and is currently burned at the ACCC's existing steam plant. The proposed TCP will be replacing the existing ACCC steam plant and provide steam and power to the ACCC facility.

(5) For combustion processes, list capacity (tonnes/year), fuel type and grade:
Capacity: 2.29x10(7) MMBtu/year Fuel Type: natural gas Fuel Grade: western Canada pipeline

(6) Contact for technical and design information:

Phone Number:  (416) 962-4411  
Fax Number:      (416) 662-1437

(7) Estimated annual quantities of the following pollutants released to the atmosphere (tonnes per year):

SO2 :           38
PM :            60
NOx :           696
VOC :          93
CO :           302

Note: These are maximum annual rates, assuming 24 hr/day, 365 day/yr operation at 100% load for the gas turbine, duct burner and the two auxiliary boilers.

(8) List hazardous air pollutants with emissions estimates (tonnes/year) for any hazardous pollutants with expected annual emission rates of greater than 1 tonne per year:
Formaldehyde: 5.3 tonnes/year Ethane: 9.4 tonnes/year Butane: 6.4 tonnes/year Hexane: 5.4 tonnes/year Pentane: 7.9 tonnes/year Propane: 4.8 tonnes/year Note: These are maximum annual rates.